Product Overview
Description and Application
These low limit controllers are SPDT devices
designed for use on HVAC equipment requiring
low-temperature control and/or indication in duct
work or on heating/cooling coils.
On a decrease in sensed temperature, the unit will
actuate at its setpoint. The CTE-3007 (manual-reset
model) will reset when the reset buon is pushed
and the sensed temperature is at least 5° F (2.8°
C) above the setpoint. The CTE-3006 (automatic-
reset model) will automatically reset when sensed
temperature rises 5° F above the setpoint. A test
lever, located under the cover, allows the unit to be
manually actuated to facilitate system checkout.
For use in stratied airstreams, the unit will respond
to the lowest temperature sensed along any one foot
section of the sensing element.
To aid installation of capillaries, HMO-4523
capillary-mounting clips (ordered separately) are
recommended.
Features
◆ SPDT switching action
◆ 20-foot capillary
◆ Responsive to lowest temperature sensed along
any one foot section of capillary element
◆ Setpoint visible through front cover and adjust-
able from top of case
◆ Manual and automatic reset models available
◆ Reset disabled until temperature rises at least 5°
F (2.8° C) above the setpoint
◆ Manual testing lever inside the cover
Specifications and design subject to change without notice.
CTE-3006/3007
Low Limit Controllers, SPDT
Specifications
Description and Application 1
Features 1
Specifications 1
Dimensions and Details 2
Accessories 2
Range 35 to 68° F (1.7 to 20° C)
Dierential 4.5° F xed (2.5° C)
SwitchAction SPDT, snap-acting
Element
3/32" (2.4 mm) diameter,
20-foot (607 cm) length,
vapor-lled, tin-plated copper
capillary, max. temperature
300° F (149° C)
ElectricalRatings
Inductive 24 FLA (Full Load Amperes)
@ 120/240 VAC
144 LRA (Locked Rotor
Amperes) @ 120/240 VAC
2 HP @ 120 VAC, 3 HP @ 240
VAC
Pilot Duty 720 VA max. @ 120 to 600 VAC,
144 VA max. @ 24 VAC
Approvals CUL US Listed, CE Compliant,
RoHs compliant
Weight 1.0 lbs. (0.45 kg)
Materials Plated steel case, plastic cover
Mounting Surface mount with capillary
installed in horizontal serpen-
tine paern
TemperatureLimits
Operating –60 to 160° F (–51 to 71° C)
Shipping –60 to 160° F (–51 to 71° C)
Models
CTE-3006 Automatic reset
CTE-3007 Manual reset
Accessories
HMO-4523 Capillary Clip (ordering about 5
clips per unit is recommended)