Description
The analog electronic KMC CSP-5001/5002s are
pressure-independent combination controller-
actuators, designed primarily for use on variable-air-
volume terminal units. Airow is sensed by using a
single or multi-point dierential (velocity) pressure
measuring station or pitot tube (such as an SSS-1000
series airow sensor). Designed with an onboard
ow-through sensor using twin platinum resistance
temperature detectors, these models are capable of
controlling a velocity setpoint from 0 to 3,300 fpm
with an accuracy of 3%.
The CSP-5001 (CCW to close) and CSP-5002 (CW to
close) oer full-range ow control of VAV terminal
units when used with the CTE-5202 and CTE-5100
series room thermostats. Air velocity ow control
limits may be set at the thermostat or internal to
the CSP-5001/5002. The actuator section provides
adjustable stops, magnetic clutch, and a gear
disengagement buon. Internal status LEDs indicate
green for opening and red for closing.
Available control options include proportional or
two-position (hot water or electric) reheat, change-
over, dual minimums, fan induction, dual duct, and
automation interface.
Features
◆ Onboard ow-through sensors with twin plati-
num resistance temperature detectors
◆ Setpoint accuracy of 3% from 0 to 3,300 fpm
◆ Adjustable stops
◆ Magnetic clutch
◆ Gear disengagement buon
◆ Internal LED rotation status indicators
CSP-5001/5002
VAV Flow Controller-Actuators
Accessories
Air Flow Sensors
SSS-10x2 1 sensing point, 3-5/32" length
SSS-10x3 2 sensing points, 5-13/32" length
SSS-10x4 3 sensing points, 7-21/32" length
SSS-10x5 4 sensing points, 9-29/32" length
Thermostats
CTE-5100 Series Thermostats
CTE-5202 Thermostat w/ LCD display
Miscellaneous
HFO-0011 Adaptor for 3/8" shaft
HMO-1003 Replacement non-rotation
bracket
HMO-4520 Compression connector for
plenum cable
HSO-5001 Test leads
Models
CSP-5001 CCW to close
CSP-5002 CW to close
NOTE: Factory-set rotation direction of either
model can be reversed by changing a
jumper position.
NOTE: For detailed applications, cross-references,
troubleshooting, and other information,
see the CSP-5001/5002 Applications Guide
and the CTE-5202 Applications Guide. See
also the CSP-4702.