Application Guide
CSP-5001/5002 VAV Flow Controller-Actuators 6 Applications Guide, Rev. B
Controller Calibration
Minimum and Maximum Flow Limits
Minimum and maximum ow limits are oen set
at the CTE-5100 series thermostat (see the CTE-5100
Series Thermostat Reference section). If desired, the
minimum and maximum limits can be dened by
adjusting the appropriate setpoints within the CSP-
5001/5002 controller (see below) instead, but do not
try to set the limits at BOTH the controller and the
thermostat (or else the limits will not reect either
the controller’s or the thermostat’s limits).
To set the velocity limits at the CSP:
1. Remove the access door by pulling back on the
door’s tab and liing upward.
2. Connect a voltmeter to the meter taps (using
HSO-5001 test leads).
3. Move the jumper from the NOR (normal) position
(two le-most pins) to the MIN position (two
right-most pins).
4. Adjust the MIN potentiometer for the desired
minimum voltage.
NOTE: MIN must be adjusted rst.
5. Move the jumper to the MAX position (two center
pins).
6. Adjust the MAX potentiometer to the desired
maximum voltage.
7. Return the jumper to the NOR position.
VNOM (CFM) Range Setting
The CSP range is factory-calibrated with the
VNOM potentiometer centered. Using any SSS-
1002/1003/1004/1005 series velocity pickup, tubing,
and reducers, the CSP will have a range of 0–3,300
fpm with a 0–10 volt DC reset control signal.
Leaving the VNOM at the factory seing is recom-
mended! Changing the VNOM potentiometer from
the factory seing will alter the calibration between
the “IN” and “OUT” voltages. However, the VNOM
can be adjusted to match 0–10 volts to a specic ve-
locity range if desired.
NOTE: In the controller, VNOM stands for
“NOMinal Volumetric ow rate.”
To set the VNOM range to a dierent range than
the factory default (a new curve):
1. Remove the access door by pulling back on the
door’s tab and liing upward.
2. Supply the desired high end of range velocity to
the “H” and “L” ports.
3. Connect a voltmeter between the “OUT” and “–”
terminals and adjust the VNOM potentiometer
until the voltage equals 10 volts DC.
To return the VNOM range to the factory default
range of 0–3300 fpm as illustrated in the chart on
page 3:
1. Remove the access door by pulling back on the
door’s tab and liing upward.
2. Supply or simulate a 3300 /min velocity (or 0.5"
delta P) at the “H” and “L” ports.
3. Connect a voltmeter between the “OUT” and “–”
terminals and adjust the VNOM potentiometer
until the voltage equals 10 volts DC.
OR
2. Measure the velocity of the airow measured by
the “H” and “L” ports.
3. Connect a voltmeter between the “OUT” and “–”
terminals and adjust the VNOM potentiometer
until the voltage at the meter equals the
corresponding voltage from the chart on page
3. The higher the ow, the more accurate the
adjustment.