Application Guide

CSP-5001/5002 VAV Flow Controller-Actuators 19 Applications Guide, Rev. B














 



   



Dual Duct, Minimum Air From Cold Duct
NOTE: Connect jumper from T2 to R1 (shown) to
override cooling minimum to zero, upon
call for heating. Connect R2 to ground (–).
NOTE: Connect jumper from T1 to R2 (not shown)
to override heating minimum to zero upon
call for cooling. Connect R1 to ground (–).
Dual duct applications can use two CSP-5001 series
controllers with a dual-setpoint (RA/DA) thermostat,
as shown below. In this application the CSP-5001
controllers are mounted separately on the cold and
hot air duct dampers with each utilizing it’s own
ow sensor.
The cold-deck controller receives the “T1” signal
from the thermostat while the hot-deck controller
receives its requested ow signal from “T2.” Both
units can be set independently for minimum and
maximum ow seings. In addition, by using the
“R1” or “R2” override terminal on the thermostat,
minimum ow can be overridden to zero upon a call
for heating (or vise-versa).




































(Former Ref. # APE-2-5001)