Application Guide
CSP-5001/5002 VAV Flow Controller-Actuators 18 Applications Guide, Rev. B
Cooling with Hot Water Reheat
This application uses a CTE-5104 thermostat with
a VEP-43/VEB-46 series 3-way hot water valve to
control temperature in the conditioned space. The
valve shown below uses the (discontinued) MEP-
5062 or (fail-safe) MEP-5372 actuator for reheat
control.
With 0 VDC from the thermostat, the mixing valve
bypasses water from the supply to the return. As the
thermostat voltage increases, water begins owing
into the coil to allow heated air into the space. At 2°
below setpoint the full ow is sent through the coil.
NOTE: Jumper “T2” to “R2” for automatic
auxiliary ow for heating.
(Former Ref. # APE-1-5017)