Application Guide

CSP-5001/5002 VAV Flow Controller-Actuators 12 Applications Guide, Rev. B
Auto, Override to Fully Closed, or Override to Fully Open
The “Override to Fully Closed” wiring diagram
below allows the CTE-5101 thermostat to control the
CSP-5001 controller as normal (Auto) or override
ow seing on the CSP-5001 to fully closed.
The SPDT relay switches to select between the two
modes (Auto/Fully Closed). In the relay position
shown, the controller will override the ow seing.
(Jumping “–” and “IN” drives the actuator fully
closed.)
When the relay switches, the thermostat will control
the VAV box based on demand (Auto).








   





The “Override to Fully Open” wiring illustration
below allows the CTE-5101 thermostat to control the
CSP-5001 controller as normal (Auto) or override the
ow seing on the CSP-5001 to fully open.
The SPDT relay switches to select between the two
modes (Auto/Fully Open). In the relay position
shown, the controller will override the ow seing.
(Jumping “16 VDC” and “IN” drives the actuator
fully open.)
When the relay switches, the thermostat will control
the VAV box based on demand (Auto).








   




