Product Overview
Table Of Contents
© 2014 KMC Controls, Inc. 036-035-04G
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
For information on mounting, wiring, and other
information, see the CSP-4702 Installation Guide.
CSP-4702
24 VAC CTE-5202
(Used in VAV
applications but
not in static
pressure bypass
applications)
Damper
SSS-100x Sensor
1/4-Inch Tubing
SET
POINT
3/8" Tubing
3/8" to 1/4" Union Adapters
Applications and More Information
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
~
–
(Phase)
(Neutral)
(To Flow Sensor)
(5K–10K
Ohm Resistor
between AI1
and Common
for Heating
Mode Only)
CSP-4702
Controller-Actuator
24 VAC @ 5 VA
For sample applications with the CTE-5202 thermo-
stat, see the CTE-5202 Applications Guide.
NOTE: When using SSS-101x sensors, the 3/8"
tubing and adapters are unnecessary.
For use as a static pressure controller in AHU/RTU
bypass applications, see the CSP-4702 Static Pres-
sure (Bypass) Control Application Guide.
NOTE: Air ow volume in VAV boxes (with
supplied air ow sensors) is determined
from the dierential pressure by the
formula Volume (cfm) = K√DP (the K factor
of the VAV box multiplied by the square
root of the dierential pressure in “wc”).
The K factor should be in the information
supplied by the VAV box’s manufacturer.
For CSP-4702 usage with KMC SSS-1000
series sensors, see the sensor K factors and
other information in the SSS-1000 Series
Installation Guide.