Description and Application
The compact analog electronic CSP-4702 is a com-
bination controller-actuator designed primarily for
use on pressure-independent VAV (Variable Air
Volume) terminal units. It also has applications as
an electronic static pressure (bypass) controller.
Dierential air pressure is sensed by an internal
digital CMOS sensor connected via 1/4" FR tubing
to an SSS-1000 series airow sensor. The 0 to 2" wc
(0 to 500 Pa) dierential pressure sensor is internally
linearized and temperature compensated for high
accuracy down to very low pressures.
The CSP-4702 oers full-range ow control of VAV
terminal units when used with the CTE-5202 elec-
tronic room thermostat. (For sample applications
with that thermostat, see the CTE-5202 Applications
Guide.) Air ow control limits may be set at the
thermostat or internal to the CSP-4702. An adjust-
able mechanical stop is also included.
The CSP-4702 accepts a 2 to 10 VDC control signal
from the thermostat. “Anti-jier” circuitry signi-
cantly reduces hunting and needless wear on the
actuator and damper components (from unnecessary
miniscule position changes caused by undamped
analog input signals). It also provides a 16 VDC
output supply to power the thermostat and a 1 to
5 VDC voltage output that is proportional to the
sensed dierential pressure.
The CSP-4702 mounts directly to 1/4- to 5/8-inch (6
to 16 mm) round shafts or 1/4- to 7/16-inch (6 to 11
mm) square shafts, eliminating the need for ex-
pensive and complicated linkages. (An HLO-4001
crank arm kit is available, however, for when di-
rect mounting is impractical.) An HMO-4002 non-
rotation bracket, to prevent lateral movement, is
included. (An HMO-4001 non-rotation “T” bracket
is also available for spanning open distances.) A gear
disengagement buon allows easy manual position-
ing of the actuator.
For troubleshooting and setup, internal status LEDs
(under the cover) indicate green for opening and red
for closing. Factory-set clockwise-to-close rotation
can be reversed by changing a jumper position.
Specifications and design subject to change without notice.
Description and Application 1
Features 1
Specifications 2
Accessories 3
Applications and More Information 4
Features
◆ Pressure-independent VAV (Variable Air Volume)
or static pressure (bypass) control applications
◆ Onboard digital CMOS dierential pressure sen-
sor, internally linearized and temperature com-
pensated, provides high accuracy down to very
low pressures
◆ 1 to 5 VDC voltage output, proportional to the
sensed dierential pressure
◆ 16 VDC output to supply power to a thermostat,
and input for 2 to 10 VDC control signal from a
thermostat
◆ Adjustable mechanical end stop
◆ Internal LED rotation status indicators for trou-
bleshooting and setup
◆ Rotation-to-close direction reversible via jumper
◆ Gear disengagement buon for easy manual po-
sitioning
◆ Mounts directly to 1/4- to 5/8-inch round shafts
or 1/4- to 7/16-inch square shafts, eliminating the
need for expensive and complicated linkages
CSP-4702
Analog Differential-Pressure VAV Controller/Actuator
(Size Shown
Relative to a
Quarter)