Applications Guide

CSP-4702 Static Pressure (Bypass) Control 1 Application Guide, AN0114A Rev. A
Procedure
For static pressure applications:
1. Connect the “HI” port of the CSP-4702 to the
pitot tube or SSS-1000 series sensor (see Air Pres-
sure Connection on page 3).
2. Connect the 24 VAC power (see Wiring Connec-
tions on page 2). Optionally connect remote
setpoint and pressure reading devices to a BAS
(Building Automation System) controller.
3. Set the MIN ow limit to the desired bypass
pressure setpoint (see Bypass Pressure Setpoint
on page 3).
4. Set the rotation direction to CW or CCW for the
open” direction (instead of “close” direction—
see Rotation Direction on page 2).
Application Guide
CSP-4702
Static Pressure (Bypass) Control
Contents
Introduction ...................................................................1
Procedure .......................................................................1
Wiring Connections .......................................................2
Rotation Direction .........................................................2
Air Pressure Connection .................................................3
Bypass Pressure Setpoint ................................................3
Troubleshooting .............................................................4
More Information ........................................................... 4
Important Notices ..........................................................4
Introduction
Besides VAV applications, the CSP-4702 can also act
as a static pressure controller in such applications
as RTU/AHU bypass control. It is not connected to a
thermostat for this application.
In bypass applications, the damper should open
(decreasing the pressure) if the pressure input
signal is higher than the setpoint. This is opposite
of VAV applications, in which the damper closes
(decreasing the ow) if the pressure input signal is
higher than the setpoint.
CSP-4702
24 VAC
Bypass Damper
To Low Pressure Port
on Pitot Tube
OR
to H or L Port on
SSS-100x Sensor
(Mounted Perpendicular
to Air Flow)
To HI Port 1/4" Tubing
Optional Remote Setpoint Input (2–10 VDC proportional to 0–2" wc) from BAS
Optional Pressure Reading Output (1–5 VDC proportional to 0–2" wc) to BAS
SSS-100x Sensor
3/8" Tubing
(to H or L)
3/8" to 1/4"
Union Adapter
Air Handler Unit (AHU)
or
Roof Top Unit (RTU)
Supply Air
Return Air