Product Overview
Table Of Contents
Specifications
Damper Action Factoryset@NO,eldadjust-
ableforNCorNO
Thermostat Action Directorreverseactionfor
heatingorcooling
Main Air Pressure 15to30psi(103to207kPa)
Max. Signal Pressure6"wc(1493Pa)appliedto
eitherport(HorL)
Reset Span Factory-set@5psi(34.5kPa),
adjustablebetween0and10
psi(0and69kPa)ifnecessary
Material Flame-retardantplastic
Details
© 2012 KMC Controls, Inc. 213-035-01D
KMC Controls, Inc.
19476IndustrialDrive
NewParis,IN46553
574.831.5250
www.kmccontrols.com;info@kmccontrols.com
All dimensions are in inches (mm).
CAUTION
Pneumatic devices must be
supplied with clean, dry control
air. Any other medium (e.g., oil
or moisture contamination) will
cause the device to fail.
Model Selection Chart
Model #
Reset Start Point
Factory Set (all eld-
adjustable 0–10 psi)*
Dierential
Pressure
Min.
Setpoint
Max.
Setpoint
Output
Sensitivity
Air Consumption
CSC-3011-10
CSC-3017-16**
8psi(55kPa)
0to1.0"wc
(249Pa)
0to1.0"wc
(249Pa)
Min.to1.0"
wc(249Pa)
5psi/0.02"wc
(35kPa/5Pa)
28.8scim@20psi
(7.87mL/s@138kPa)
CSC-3021-10 3psi(21kPa)
CSC-3023-10 10psi(69kPa)
CSC-3026-10 3psi(21kPa)
0to2.0"wc
(498Pa)
0to2.0"wc
(498Pa)
Min.to2.0"
wc(498Pa)
5psi/0.04"wc
(35kPa/10Pa)
CSC-3016-10
8psi(55kPa)
CSC-3025-10
46.1scim@20psi
(12.59mL/s@138kPa)
*Resetspan,forallmodels,isfactory-setat5psi(34.5kPa),adjustablebetween0and10psi(0and69kPa).
**TheCSC-3017-16isidenticaltotheCSC-3011-10,butitdoesnotcomewithamountingbracketortheKMClogo.
Temperature Limits
Operating 40to120°F(4to49°C)
Shipping –40to140°F(–40to60°C)
Weight 11oz.(312grams)
Approvals RoHScompliant