Applications Guide

CSC-3000 Series Pneumatic VAV Reset Volume Controllers 11 Applications Guide, Rev G
Cooling with Heating Valve
DA Thermostat, NO or NC Damper, and NO Hot Water Valve
RA Thermostat, NO or NC Damper, and NC Hot Water Valve
LO STAT = Min. Flow
HI STAT = Max. Flow
Reset Range = 8 to 13 psi
Hot Water Valve = NO
Spring Range = 3 to 8 psi
LO STAT = Max. Flow
HI STAT = Min. Flow
Reset Range = 3 to 8 psi
Hot Water Valve = NC
Spring Range = 8 to 13 psi