Applications Guide
Table Of Contents
CSC–2000 Series Pneumatic VAV Reset Volume Controllers 3 Applications Guide
The table below illustrates the appropriate model for
each application. If replacing a CSC–2001-22 or CSC–
2002-22 (now obsolete), use the CSC–2001, CSC–2002,
CSC–2003, or CSC–2004 and mount appropriately.
Models and Specifications
Output Sensitivity 0 to 1" range unit,
5 psig/0.02" wg (35 kPa/5 Pa)
0 to 2" range units,
5 psig/0.04"wg (35 kPa/10 Pa)
Main Air Pressure 15 to 30 psig (103 to 207 kPa)
Max. Signal Pressure 6" wg (1493 Pa) applied to
either port (X or Y)
Material ABS (beige or gray)
UL Flame Class 94 HB
Output Capability 0 to supply pressure
Weight 7.5 oz. (213 grams)
Temperature Limits
Operating 40° to 120° F (4° to 49° C)
Shipping –40° to 140° F (–40° to 60° C)
Direct Acting (Beige Controllers) for Normally Open Dampers
Model
Thermostat Required Setpoint Range
Reset Pressure
Band
Air Consumption
0–10
Molded
Dial
For
Cooling
For
Heating
Minimum Maximum
CSC-2001
Direct
Acting
Reverse
Acting
0 to 1.0" wg
(249 Pa)
Min. plus 1"
wg (249 Pa)
8 ±0.5 to 13 psig
(55 ±3.5 to 90 kPa)
14.4 scim @ 20 psig
(3.93 mL/s @ 138 kPa)
Yes
CSC-2003 14.4 scim @ 20 psig
(3.93 mL/s @ 138 kPa)
No
molded
plastic
dial—
has
paper
label
instead
CSC-2007 11.5 scim @ 20 psig
(3.1 mL/s @ 138 kPa)
CSC-2009
0 to 2.0" wg
(498 Pa)
Min. plus 2"
wg (498 Pa)
14.4 scim @ 20 psig
(3.93 mL/s @ 138 kPa)
CSC-2017 11.5 scim @ 20 psig
(3.1 mL/s @ 138 kPa)
Reverse Acting (Gray Controllers) for Normally Closed Dampers
Model
Thermostat Required Setpoint Range
Reset Pressure
Band
Air Consumption
0–10
Molded
Dial
For
Cooling
For
Heating
Minimum Maximum
CSC-2002
Reverse
Acting
Direct
Acting
0 to 1.0" wg
(249 Pa)
Min. plus 1"
wg (249 Pa)
3 ±0.5 to 8 psig
(21 ±3.5 to 55 kPa)
14.4 scim @ 20 psig
(3.93 mL/s @ 138 kPa)
Yes
CSC-2004 14.4 scim @ 20 psig
(3.93 mL/s @ 138 kPa)
No
molded
plastic
dial—
has
paper
label
instead
CSC-2008 11.5 scim @ 20 psig
(3.1 mL/s @ 138 kPa)
CSC-2010
0 to 2.0" wg
(498 Pa)
Min. plus 2"
wg (498 Pa)
14.4 scim @ 20 psig
(3.93 mL/s @ 138 kPa)
CSC-2018 11.5 scim @ 20 psig
(3.1 mL/s @ 138 kPa)
Direct Acting BEIGE units (CSC–2001/2003/2007/
2009/2017) are designed for normally open dampers
with direct-acting thermostats for cooling and re-
verse-acting thermostats for heating.
Reverse Acting GRAY units (CSC–2002/2004/2008/
2010/2018) are designed for normally closed damp-
ers with reverse-acting thermostats for cooling and