Product Overview

Details
Features
Separate adjustments for minimum and maxi-
mum airow seings.
CSC-2001/2003/2007/2009/2017 are designed for
normally open dampers with direct-acting ther-
mostats for cooling and reverse-acting thermo-
stats for heating.
CSC-2002/2004/2008/2010/2018 are designed for
normally closed dampers with reverse-acting
thermostats for cooling and direct-acting thermo-
stats for heating.
CSC-2001/2002 are equipped with 0 to 10 molded
plastic reference dials; others have paper labels.
© 2014 KMC Controls, Inc. 205-035-01F
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com;
info@kmccontrols.com
Specifications
Output Sensitivity 0 to 1" range unit,
5 psi/0.02" wc (35 kPa/5 Pa)
0 to 2" range units,
5 psi/0.04" wc (35 kPa/10 Pa)
Main Air Pressure 15 to 30 psi (103 to 207 kPa)
Max. Signal Pressure 6" wc (1493 Pa) applied to
either port (X or Y)
Material ABS (beige or gray)
Output Capability 0 to supply pressure
Weight 7.5 oz. (213 grams)
Temperature Limits
Operating 40 to 120° F (4 to 49° C)
Shipping –40 to 140° F (–40 to 60° C)
Approvals RoHS compliant
Mounting Position
The controllers are position sensitive. The min.
and max. ow limits must be set (calibrated) in the
same position the controller will be mounted. The
CSC-2001/2002 (with molded plastic dials) must be
mounted horizontally with dials facing up. The CSC-
2003 through CSC-2018 may be mounted horizon-
tally (preferred), with the adjustment knobs up or
down, or mounted vertically.
Connections Adjustments
All dimensions in inches (mm).
CAUTION
Pneumatic devices
must be supplied with
clean, dry control air.
Any other medium
(e.g., oil or moisture
contamination) will
cause the device to fail.
Accessories/Repair Parts
HFO-0006 In-line control-air lter
HMO-4505 Mounting bracket
ICI-1005 Pressure gauge
SSS-1000 Series Flow sensors