Applications Guide

CEP-4000 Series VAV Flow Controller-Actuators 21 Applications Guide
Heating/Cooling Constant Volume w/ Hot Deck Make-Up
NOTE: Minimum and maximum to be set on the
cooling side for VAV.
Constant volume seing must be equal to
or greater than cooling maximum.
Set constant volume on the heating side by
adjusting maximum full counter-clockwise
and adjusting minimum for the desired
constant volume.
The following application is designed for dual-duct
installations requiring a constant volume of airow
into the space at all times. In this application, a
single-duct cooling controller is mounted on the
cold air duct, and its minimum and maximum
ow is reset by the room thermostat. A second
“slave” controller is mounted on the hot air duct
as a constant volume unit, with the ow sensor
measuring downstream “total ow” into the
space (the “slave” controller has no reset from the
thermostat).
In summary, as the cold deck resets from maximum
to minimum ow, the hot deck controller senses
a decrease in “total ow” to the space, opens the
hot air duct to compensate, and thus maintains a
constant combined airow into the room.



















 
























(Former Ref. # APE-2-4005)