Applications Guide

CEP-4000 Series VAV Flow Controller-Actuators 19 Applications Guide































Damper Tracking (Master/Slave)
The conguration is used for special applications
where a dierential pressure is needed (either
positive or negative). The CTE-1101 DA thermostat
controls the “master” controller-actuator and an
REE-1013 relay is utilized to control the “slave”
controller. The relay takes the voltage reading from
the master controller and repeats it to the slave
controller plus or minus a given oset.
As an example, the master controller is supplying
a velocity of 450 fpm (4.0 VDC on terminal 6), and
the relay commands the slave controller to exhaust
550 fpm (4.1 VDC). The amount of voltage “oset”
would be 0.10 VDC to set-up the REE-1013. See the
Voltage/Velocity Correlation section.












(Former Ref. # APE-5-4001)