Applications Guide

CEP-4000 Series VAV Flow Controller-Actuators 12 Applications Guide
VAV Single Duct Cooling/Heating Applications
Cooling
CTE-1001/1002/1101 single-setpoint thermostats are
designed for use with CEP-4000 series electronic
VAV controllers to operate damper boxes and/or
valves in the HVAC system. A “requested ow”
voltage signal (T1 or T2) is wired to the CEP-4000
series controller to adjust airow from minimum to
maximum ow according to space demand. Both
minimum and maximum ow limit adjustments can
be made at the thermostat.
An additional “unrestricted” output (T3 or T4) is
not aected by min./max. limits and can be used to
operate reheat equipment or other control devices by
using REE-series relays. The CTE-1001/1101 is Direct
Acting (DA) reset, and the CTE-1002 is Reverse
Acting (RA) reset.
(Former Ref. # APE-1-4001)













Cooling Max.
Cooling Min.
0 fpm
Setpoint
(Colder Room Temperature Warmer)
3000
fpm
Air
Flow
Min.3000 fpm
03000 fpm