CEP-4000 Series VAV Flow Controller-Actuators 14 Applications Guide
Cooling with 3-Stage Reheat
Chart 1 Chart 2
The CTE-1004 electronic thermostat is a dual setpoint
thermostat for heating (RA) and cooling (DA) ap-
plications. The application below uses an SSE-1000
series sensor, an REE-4001 relay module, and three
24 VAC contactors for three stages of reheat.
The transformer must supply a minimum of 14 VA
plus the requirements for the reheat contactor coils
(10 VA maximum per stage).
Chart 1 below shows the jumper between “T2”
and “A” on the thermostat was removed to prevent
auxiliary ow. (If auxiliary ow is not being used
you should rotate the auxiliary potentiometer fully
CCW to make sure it will not have an eect.) As the
temperature drops below setpoint, the rst stage of
reheat begins. If the temperature continues to drop,
the second stage begins, and nally the third stage if
necessary.
When the jumper is le on for auxiliary ow (Chart
2), a second minimum ow (Aux. Flow) may be set
before enabling the reheat stages.
(Former Ref. # APE-1-4005)