Install Instructions
KMC Controls
P.O. Box 497
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
730-019-01
Adjustments and Calibration
1. Choose a setpoint between 2–25 psi (14–172 Kpa).
NOTE: The units have a 2 psi fixed differential
2. Turn the setpoint adjustment wheel until the bottom of the
wheel lines up with the signal pressure listed on the front of
the switch.
3. Replace cover on models CCE-1001/1002
NOTE: A gauge may be installed before completing step 2 to
calibrate the unit to an actual signal pressure.
Maintenance
No routine maintenance is required.
Each component is designed and manufactured for reliability
and performance. Careful installation and use will ensure long
term dependability.