Owner's manual

CCC-1001/1002 (Dual Input Receiver Controllers) 4 Installation Guide
© 2009 KMC Controls, Inc. 218-019-01E
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com; info@kmccontrols.com
Competitor Cross-Reference
The CCC-1002 can replace many competitor single/
dual-input receiver/controllers such as:
Barber-Colman (Schneider Electric) RKS-
1001/2001/3002/4002
Honeywell RP908A/RP908B/RP920A/RP920B
Johnson T-9000 and T-5801/5802
Robertshaw (Schneider Electric) P341 and 2341
Siemens 185 and 195 series
A cross-reference of corresponding piping for some
of these controllers is shown in the chart below.
NOTE: External restrictor HFO-0022 might be
required if replacing a receiver/controller
using internal restrictors.
M
M
M
M
Primary Transmitter
(sensed medium, e.g., hot water)
Restrictor
Restrictor
Optional Secondary Transmitter
(sensed medium, e.g., outside air)
Optional Remote
Setpoint Adjust
Regulator
Controlled
Device
Primary Input: 1
Output Signal: B
Main Air: MAIN
Secondary Input: 3
Remote Setpoint: 2
Ports
KMC
Barber-
Colman
Honeywell Johnson Robertshaw Siemens
CCC-1002 RKS RP908 RP920 T-5800 P341 P541 195
Main Air MAIN M M 1 S M M S
Output Signal B B-c B 2 O B B C
Primary Input 1 1 1 3 CV 1 S 1 or 2
Secondary Input 3 2 2 5 M 3 R 1 or 2
Remote Setpoint 2 RSPA CPA 9 SP 2 C 3