Procedure Steps STE display
2. With a flow hood, measure the actual
airflow.
3. Press the
Set
Point
button to advance to the entry
display. SMAX stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the
Set
Point
button to save the measured
airflow. The display advances to SMIN.
7 Measure and enter the
actual minimum
secondary airflow
The display begins flashing SMIN and also
displays the actual airflow at the bottom.
Note: The airflow displayed by the STE-8000
in this step is the actual, uncorrected airflow.
1. Wait for the minimum airflow value to
stabilize.
2. With a flow hood, measure the actual
airflow.
3. Press the
Set
Point
button to advance to the entry
display. SMIN stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the
Set
Point
button to save the measured
airflow. The display advances to SEC.
SMIN
OO
8 Advance or exit
1. Press the or buttons to select one of the
following:
l PRI to balance the primary VAV for dual
duct systems
l BACK to choose another configuration
function.
l EXIT to return to the temperature display.
2. Press the
Set
Point
button to select the next
function.
SEC
The airflow balancing procedure (continued)
Section 5: Balancing airflow KMC Controls, Inc.
43 Revision G