Install Instructions

Table Of Contents
Set the airflow setpoints
The airflow setpoints set the airflow limits for the VAV terminal unit.
l Airflow heating and cooling minimum and maximum limits
l Auxiliary flow setpoint (optional)
l Minimum and maximum fan speeds (optional)
Setting the airflow setpoints requires entering Password 2 which is described in the topic
Getting started with configuration on page 24.
Note: If the VAV unit is a heat only or cooling only unit, the airflow setpoints for the unused mode
must be set within the range of the mode in use. Failure to set the unused setpoints
correctly will result in unpredictable or erroneous air balancing settings.
Tip: Once the following procedure is started, all steps must be completed in order.
Procedure Detailed steps STE display
1 Starting display
1. Start at the temperature display.
2. Press the and buttons together.
l If Password 2 is not required, the display
changes to CNFG.
l If required, enter Password 2. The display
changes to CNFG when Password 2 is
correct.
72
12S1
PSW2
OOOO
2 Select the flow setpoint
display.
1. From the CNFG display, press the or
buttons to show the CNFG display.
2. Press the
Set
Point
button to select the CNFG options.
The display changes to STPT.
3. Press the or buttons to change the
display to FLOW.
4. Press the
Set
Point
button to select FLOW. The
display changes to MNCL.
CNFG
STPT
FLOW
Procedure to set the airflow setpoints
Section 4: Configuring the controllers KMC Controls, Inc.
32 Revision G