Install Instructions

Table Of Contents
Entering system temperature setpoints and limits
The system temperature setpoints set the operational parameters and limits for the VAV
terminal unit.
The temperature setpoints include the following items.
l Minimum cooling and maximum heating setpoints
l Occupied and unoccupied cooling setpoints
l Occupied and unoccupied heating setpoints
l Changeover differential setpoint
l Standby differential setpoint
Setting the temperature setpoints requires entering Password 2 which is described in detail
in the topic Getting started with configuration on page 24.
Tip: Once the following procedure is started, all steps must be completed in order.
Procedure Detailed steps STE display
1 Start at the temperature
display.
1. Start at the temperature display.
2. Press the and buttons together.
l If Password 2 is not required, the display
changes to CNFG.
l If required, enter Password 2. The display
changes to CNFG when Password 2 is
correct.
72
12S1
PSW2
OOOO
2 Select the setpoint
display.
1. From the CNFG display, press the or
buttons to show STPT.
2. Press the
Set
Point
button to select the CNFG options.
The display changes to STPT.
3. Press the
Set
Point
button to select STPT. The
display changes to MIN.
CNFG
STPT
3 Set the minimum cooling
setpoint.
This setpoint limits the lowest temperature that
a user can enter as the active setpoint.
MIN
68O
Procedure to set the temperature setpoints
SimplyVAV Section 4: Configuring the controllers
Revision G 25