Installation Guide Manual
Cooling or heating
without reheat
The BAC-8001 is configured for single-duct cooling VAV control without
reheat. Connect the controller as shown in the illustration Cooling or heating
application drawing on page 50. A BAC-8005 or BAC-8205 may also be used
for this application.
For cooling and heating, a duct temperature sensor is required for Discharge
Air Temperature limiting and automatic changeover. See the topic Advanced
options on page 37 for instructions to enable Discharge Air Temperature
limiting.
Submittal sheets for several variations of this application are available from
the Resources page at www.SimplyVAV.com.
Illustration 6–1 Cooling or heating application drawing
24 VAC
Duct
Temp
Sensor
ON CTS
1 2
COMM
READY
AI1
AI5
GND
AO4
AO3
SC
BO8
BO5
BO6
SC
BO7
24VAC
AI6
GND
AI7
T-STAT/
SENSOR
-A
+B
S
EOL
BACnet MS/TP
Section 6: Application drawings SimplyVAV
50 Revision E