Installation Guide Manual

Procedure Steps STE display
5 Advance or exit
1.
Press the or buttons to select one of the
following:
SEC to balance the secondary VAV for dual
duct systems. Choosing SEC advances to
the SMAX display. This is available only on
dual duct models.
BACK to choose another commissioning
function
EXIT to return to the temperature display.
2.
Press the
Set
Point
button to select the next function.
PRI
SEC
6 Measure and enter the
actual maximum
secondary airflow
The display begins flashing SMAX and also
displays the actual airflow at the bottom.
Note: The airflow displayed by the STE-8000
in this step is the actual, uncorrected airflow.
1.
Wait for the maximum airflow value to
stabilize.
2.
With a flow hood, measure the actual airflow.
3.
Press the
Set
Point
button to advance to the entry
display. SMAX stops flashing.
4.
Press the or buttons to enter the
measured airflow.
5.
Press the
Set
Point
button to save the measured
airflow. The display advances to SMIN.
SMAX
OO
The airflow balancing procedure (continued)
Section 5: Balancing airflow SimplyVAV
46 Revision E