Installation Guide Manual
Procedure Steps STE display
3 Measure and enter the
actual maximum primary
airflow
The display begins flashing PMAX and also
displays the actual airflow at the bottom.
Note: The airflow will attempt to stabilize on
the highest value for either the cooling or
heating maximum airflow even if only one
mode is operational.
Note: The airflow displayed by the STE-8000
in this step is the actual, uncorrected airflow.
1.
Wait for the maximum airflow value to
stabilize.
2.
With a flow hood, measure the actual airflow.
3.
Press the
Set
Point
button to advance to the entry
display. PMAX stops flashing.
4.
Press the or buttons to enter the
measured airflow.
5.
Press the
Set
Point
button to save the measured
airflow. The display changes to PMIN.
PMAX
OO
4 Measure and enter the
actual minimum primary
airflow
The display begins flashing PMIN and also
displays the actual airflow at the bottom.
Note: The airflow will attempt to stabilize on
the lowest value for either the cooling or
heating minimum airflow even if only one
mode is operational.
Note: The airflow displayed by the STE-8000
in this step is the actual, uncorrected airflow.
1.
Wait for the minimum airflow value to
stabilize.
2.
With a flow hood, measure the actual airflow.
3.
Press the
Set
Point
button to advance to the entry
display. PMIN stops flashing.
4.
Press the or buttons to enter the
measured airflow.
5.
Press the
Set
Point
button to save the measured
airflow. The display advances to PRI.
PMIN
OO
The airflow balancing procedure (continued)
SimplyVAV Section 5: Balancing airflow
Revision E 45