Installation Guide Manual

Procedure Steps STE display
1 Starting display
1.
Start at the temperature display.
2.
Press the and buttons together.
l If Password 2 is not required, the display
changes to CNFG.
l If required, enter Password 2. The display
changes to CNFG when Password 2 is
correct.
72
12S1
PSW2
OOOO
2 Select the CNFG display.
1.
From the CNFG display, press the or
buttons to advance to COMM and the BLNC
display.
2.
Press the
Set
Point
button to select BLNC. The display
advances to PRI.
3.
Press the
Set
Point
button to select PRI.
CNFG
COMM
BLNC
PRI
Table 5–1 The airflow balancing procedure
Section 5: Balancing airflow SimplyVAV
44 Revision E