Installation Guide Manual

Procedure Detailed steps STE display
2 Select the flow setpoint
display.
1.
From the CNFG display, press the or
buttons to show the CNFG display.
2.
Press the
Set
Point
button to select the CNFG options.
The display changes to STPT.
3.
Press the or buttons to change the
display to FLOW.
4.
Press the
Set
Point
button to select FLOW. The display
changes to MNCL.
CNFG
STPT
FLOW
3 Set the cooling minimum
airflow limit.
1.
Press the or buttons to set the minimum
limit for cooling airflow. The setpoint changes
in 1 CFM increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
OO
MNCL
4 Set the cooling maximum
airflow limit.
1.
Press the or buttons to set the maximum
limit for cooling airflow. The setpoint changes
in 1 CFM increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
3SO
MXCL
5 Set the axillary airflow
setpoint.
Not used for all models.
This setpoint sets the airflow for when reheat is
active auxiliary airflow.
1.
Press the or buttons to set a value for the
auxillary airflow. The setpoint changes in 1
CFM increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
200
AUXF
6 Set the heating minimum
airflow limit
1.
Press the or buttons to set the minimum
limit for heating airflow. The setpoint will
change in 1 CFM increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
OO
MNHT
Procedure to set the airflow setpoints (continued)
SimplyVAV Section 4: Configuring the controllers
Revision E 35