Installation Guide Manual
Entering system
temperature
setpoints and limits
The system temperature setpoints set the operational parameters and limits
for the VAV terminal unit.
The temperature setpoints include the following items.
Minimum cooling and maximum heating setpoints
Occupied and unoccupied cooling setpoints
Occupied and unoccupied heating setpoints
Changeover differential setpoint
Standby differential setpoint
Setting the temperature setpoints requires entering Password 2 which is
described in detail in the topic Getting started with configuration on page 26.
Tip: Once the following procedure is started, all steps must be completed in
order.
Procedure Detailed steps STE display
1 Start at the temperature
display.
1.
Start at the temperature display.
2.
Press the and buttons together.
l If Password 2 is not required, the display
changes to CNFG.
l If required, enter Password 2. The display
changes to CNFG when Password 2 is
correct.
72
12S1
PSW2
OOOO
2 Select the setpoint
display.
1.
From the CNFG display, press the or
buttons to show STPT.
2.
Press the
Set
Point
button to select the CNFG options.
The display changes to STPT.
3.
Press the
Set
Point
button to select STPT. The display
changes to MIN.
CNFG
STPT
Procedure to set the temperature setpoints
SimplyVAV Section 4: Configuring the controllers
Revision E 27