Install Instructions
Table Of Contents
- Contents
- Section 1: About the controllers
- Section 2: Installing the controllers
- Section 3: Changing the room setpoint
- Section 4: Configuring the controllers
- Section 5: Balancing airflow
- Section 6: Application drawings
- Section 7: Sequences of operation
- Section 8: System integration and networking
- Appendix A: K-factors
- Index
Communications—BACnet MS/TP
l EIA–485 operating at rates up to 76.8 kilobaud.
l Removable screw terminal block.
l Wire size 12-26AWG
l Switch selected end of line termination
Memory
l Programs and program parameters are stored in nonvolatile memory.
l Auto restart on power failure
Air flow sensor features
l Configured as BACnet analog input object.
l CMOS differential pressure 0-2 inches of water (0-500 Pa) measurement range.
Internally linearized and temperature compensated.
l Span accuracy 4.5% of reading.
l Zero point accuracy 0.0008 in. H2O/0.2 Pa at 25° C
l Barbed connections for 1/4 inch FR tubing.
Actuator specifications
Torque 40 in-lb. (4.5 N
•
m)
Angular rotation 0 to 95°
Adjustable end stops at 45° and 60° rotation
Motor timing
BAC-8001,
BAC-8005, BAC-8007
90 sec./90° at 60 Hz
108 sec./90° at 50 Hz
Motor timing
BAC-8205
60 sec./90° at 60 Hz
Shaft size Directly mounts on 3/8 to 5/8inch (9.5to16mm)
round or 3/8 to 7/16 inch (9.5to11 mm) square
damper shafts.
Regulatory
l UL 916 Energy Management Equipment
l BACnet Testing Laboratory listed as an application specific controller (ASC).
l CE compliant
l FCC Class B, Part 15, Subpart B and complies with Canadian ICES-003 Class B
This device complies with part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may
cause undesired operation.
Section 1: About the controllers KMC Controls, Inc.
8 Revision G