Install Instructions

Table Of Contents
Procedure Steps STE display
Note: The airflow will attempt to stabilize on
the lowest value for either the cooling or
heating minimum airflow even if only one
mode is operational.
Note: The airflow displayed by the STE-8000
in this step is the actual, uncorrected airflow.
1. Wait for the minimum airflow value to
stabilize.
2. With a flow hood, measure the actual
airflow.
3. Press the
Set
Point
button to advance to the entry
display. PMIN stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the
Set
Point
button to save the measured
airflow. The display advances to PRI.
5 Advance or exit
1. Press the or buttons to select one of the
following:
l SEC to balance the secondary VAV for
dual duct systems. Choosing SEC
advances to the SMAX display. This is
available only on dual duct models.
l BACK to choose another commissioning
function
l EXIT to return to the temperature display.
2. Press the
Set
Point
button to select the next
function.
PRI
SEC
6 Measure and enter the
actual maximum
secondary airflow
The display begins flashing SMAX and also
displays the actual airflow at the bottom.
Note: The airflow displayed by the STE-8000
in this step is the actual, uncorrected airflow.
1. Wait for the maximum airflow value to
stabilize.
SMAX
OO
The airflow balancing procedure (continued)
SimplyVAV Section 5: Balancing airflow
Revision G 42