Procedure Steps STE display
8 Set the automatic
occupancy mode.
Requires a discharge air
temperature sensor.
1. Press the or buttons to enable or disable
automatic occupancy.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
Enable The controller will automatically
changed to the unoccupied state when it
detects the loss of primary air supply.
Disable The controller will remain in the
occupied mode regardless of the primary
air supply.
DISABLE
AUMD
9 Set the temperature
sensor calibration
constant.
1. Press the or buttons to set the
calibration constant. The setpoint will change
in0.1 minute increments.
l For a low input reading enter a positive
correction value.
l For a high input reading enter a negative
correction value.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
OO
CALIB
10Select a new
configuration function or
exit.
1. Press the or buttons to select one of the
following:
l STPT, FLOW, BOX, or RSTR options
l BACK to choose .another configuration
function
l EXIT to return to the temperature display.
2. Press the
Set
Point
button to select the next
function.
ADVC
Procedure to set the advanced options (continued)
SimplyVAV Section 4: Configuring the controllers
Revision G 37