Procedure Detailed steps STE display
3 Set the cooling minimum
airflow limit.
1. Press the or buttons to set the
minimum limit for cooling airflow. The
setpoint changes in 1 CFM increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
OO
MNCL
4 Set the cooling maximum
airflow limit.
1. Press the or buttons to set the
maximum limit for cooling airflow. The
setpoint changes in 1 CFM increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
3SO
MXCL
5 Set the axillary airflow
setpoint.
Not used for all models.
This setpoint sets the airflow for when reheat is
active auxiliary airflow.
1. Press the or buttons to set a value for
the auxillary airflow. The setpoint changes in
1 CFM increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
200
AUXF
6 Set the heating minimum
airflow limit
1. Press the or buttons to set the
minimum limit for heating airflow. The
setpoint will change in 1 CFM increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
OO
MNHT
7 Set the heating maximum
airflow limit.
1. Press the or buttons to set the
maximum limit for heating airflow. The
setpoint will change in 1 CFM increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
3SO
MXHT
8 Set the minimum limit for
fan speed.
Not used for all models.
1. Press the or buttons to set the
minimum limit for the fan speed. The
setpoint will change in 1% increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
2O
MINF
Procedure to set the airflow setpoints (continued)
SimplyVAV Section 4: Configuring the controllers
Revision G 33