Install Instructions

Table Of Contents
Procedure Detailed steps STE display
1. Press the or buttons to set the
minimum cooling setpoint. The setpoint will
change in 0.5° increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
4 Set the maximum heating
setpoint.
This setpoint limits the highest temperature a
user can enter as the active setpoint.
1. Press the or buttons to set the
maximum heating setpoint. The setpoint will
change in 0.5° increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
MAX
78O
5 Set the occupied cooling
setpoint.
This setpoint is used as the active setpoint when
the space is occupied.
1. Press the or buttons to set the occupied
cooling setpoint. The setpoint will change in
0.5° increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
Note: This setpoint can also be changed as
described in the topic Changing the room
setpoint on page 21.
OCCL
74O
6 Set the occupied heating
setpoint.
This setpoint is used as the active setpoint when
the space is occupied.
1. Press the or buttons to set the occupied
heating setpoint. The setpoint will change in
0.5° increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
Note: This setpoint can also be changed as
described in the section Changing the room
setpoint on page 21.
OCHT
7OO
Procedure to set the temperature setpoints (continued)
Section 4: Configuring the controllers KMC Controls, Inc.
26 Revision G