Product Overview
Specifications
Air flow sensor features
CMOS dierential pressure 0-2 inches of water
(0-500 Pa) measurement range. Internally linearized
and temperature compensated.
Congured as BACnet analog input object.
Span accuracy 4.5% of reading.
Zero point accuracy 0.0008 in. H2O/0.2 Pa at
25° C
Barbed connections for 1/4 inch FR tubing.
Actuator features
All models of SimplyVAV controllers include an
integrated actuator.
Torque 40 in-lb. (4.5 N•m)
Angular Rotation 0 to 95°
Adjustable end stops
at 45 and 60° rotation
Motor Timing
BAC-8001, 90 sec./90°at 60 Hz
BAC-8005, and 108 sec./90° at 50 Hz
BAC-8007
BAC-8205 60 sec./90°at 60 Hz
Shaft size
Directly mounts on 3/8 to 5/8 inch (9.5 to 16 mm)
round or 3/8 to 7/16 inch (9.5 to 11 mm) square
damper shas.
Operating Sequences
The following SimplyVAV models are supplied with
factory included programs.
BAC-8001
Model BAC-8001 is supplied with inputs, outputs,
and sequences of operation for the following
functions.
Single duct heating and cooling VAV
Automatic heating/cooling changeover including
morning warmup
Occupancy setback—requires STE-8201
System diagnostic indicators
Airow balancing
BAC-8005 and BAC-8205
Models BAC-8005 and BAC-8205 are supplied with
inputs, outputs, and sequences of operation for the
following functions.
Single duct heating and cooling VAV
Modulating, oating, time proportional, and
staged reheat
Series and parallel fan control
Automatic heating/cooling changeover including
morning warmup
Discharge air temperature limiting
Occupancy setback—requires STE-8201
Actuator position feedback for true damper
positioning (BAC-8205 only)
System diagnostic indicators
Airow balancing
BAC-8007
Model BAC-8007 is supplied with inputs, outputs,
and sequences of operation for the following
functions.
Dual-duct VAV heating and cooling
Occupancy setback—requires STE-8201
System diagnostic indicators
Airow balancing
Uses TSP-8001 for secondary damper control
BACnet communication
Integrated peer-to-peer BACnet MS/TP network
communications.
Network speed from 9600 to 76,800 baud
Meets or exceeds ANSI/ASHRAE BACnet
Standard 135-2008 for Application Specic
Controllers.
ON CTS
1 2
1.92 in.
49 mm
6.53 in.
166 mm
4.89 in.
124 mm
4.25 in.
108 mm
0.77 in.
19 mm
6.00 in.
152 mm
2.14 in.
54 mm