Output Name Description Units
BO6 HT STAGE 1 Heating Stage 1
BO7 HT STAGE 2 Heating Stage 2
BO8 HT STAGE 3 Heating Stage3
Output objects (continued)
Value objects
BACnet value objects represent setpoints or other operational conditions in the controller.
Note: Not all objects are present in every model.
Object Name Description
AV1 SPACE TEMP Space Temperature
AV2 STPT OFFSET Setpoint Offset
AV3 ACT COOL STPT Active Cooling Setpoint
AV4 ACT HEAT STPT Active Heating Setpoint
AV5 OCC CL STPT Occupied Cooling Setpoint
AV6 OCC HT SPT Occupied Heating Setpoint
AV7 UNOCC CL STPT Unoccupied Cooling Setpoint
AV8 UNOCC HT STPT Unoccupied Heating Setpoint
AV9 MIN CL STPT Minimum Cooling Setpoint
AV10 MAX HT STPT Maximum Heating Setpoint
AV11 MIN STPT DIFF Minimum Setpoint Differential
AV12 STBY OFFSET Standby Offset
AV13 MIN COOL FLOW Minimum Cooling Flow
AV14 MAX COOL FLOW Maximum Cooling Flow
AV15 MIN HEAT FLOW Minimum Heating Flow
AV16 MAX HEAT FLOW Maximum Heating Flow
AV17 AUXILIARY FLOW Auxiliary Flow
AV18 PRI K FACT Primary K Factor
AV19 PRI CORR SLOPE Primary Correction Slope
AV20 PRI CORR OFFST Primary Correction Offset
Table 84 Analog value objects