BACnet objects
The SimplyVAV controllers are BACnet Application Specific Controller (ASC) that are
composed of standard BACnet objects. This section lists the objects that are likely to be
monitored by a standard BACnet operator workstation to verify system operation.
Caution
Changing the configuration of any object may result in
unpredictable operation of a controller and damage to
equipment that is under control of a SimplyVAV controller.
Input objects
The following BACnet input objects represent values at the physical inputs of the controller.
For wiring details, see the topic Application drawings on page 44.
Input Name Description Object type
AI1 DISCHARGE AIR Discharge Air Temperature KMC10K_Type_III
AI2 SPACE SENSOR Space Sensor KMC Type II Deg F
AI3 SETPOINT
OFFSET
Setpoint Offset TABLE_4
AI4 PRIMARY DUCT Primary Duct Pressure
AI5 SECONDARY
DUCT
Secondary Duct Pressure
Table 8–2 Input objects
Output objects
The following BACnet output objects represent values at the physical outputs of the
controller. For application specific output wiring details, see the topic Application drawings
on page 44.
Output Name Description Units
AO3 ANALOG HEAT Analog Heat 0_100%
AO4 FAN SPEED Fan Speed 0_100%
BO1 DAMPER CW Damper Clockwise
BO2 DAMPER CCW Damper Counter Clockwise
BO5 FAN Fan
Table 8–3 Output objects
Section 8: System integration and networking KMC Controls, Inc.
68 Revision G