Procedure Detailed steps STE display
5 Enter the baud
1. Press the or buttons to select a new
baud.
2. Press the
Set
Point
button is save the selected baud.
The display returns to COMM.
BAUD
384OO
6 Advance or exit
1. Press the or buttons to select one of the
following:
l BLNC or CNFG options
l EXIT to return to the temperature display.
2. Press the
Set
Point
button to select the next
function.
COMM
Procedure to set up network communications (continued)
SimplyVAV Section 8: System integration and networking