Setting up network communications
Set the network communication settings before placing a controller on the network. Setting
network settings requires entering Password 2 which is described in the topic Getting
started with configuration on page 24.
Procedure Detailed steps STE display
1 Starting display
1. Start at the temperature display.
2. Press the and buttons together.
l If Password 2 is not required, the display
changes to CNFG.
l If required, enter Password 2. The display
changes to CNFG when Password 2 is
correct.
72
12S1
PSW2
OOOO
2 Select the CNFG display
1. From the CNFG display, press the or
buttons to advance to the COMM display.
2. Press the
Set
Point
button. The display changes to
DID.
CNFG
COMM
3 Enter the device instance.
1. Press the or buttons to change the first
digit.
2. Press the
Set
Point
button to select the next digit.
Repeat for all seven digits.
3. When the
Set
Point
button is pressed for the last
digit, the display changes to MAC.
D ID
OO72O69
4 Enter the MAC address.
1. Press the or buttons to change the MAC
address.
2. Press the
Set
Point
button to save the selected MAC
address.
The display changes to BAUD.
MAC
11
Table 8–1 Procedure to set up network communications
Section 8: System integration and networking KMC Controls, Inc.