Install Instructions

Table Of Contents
Procedure Steps STE display
2 Select the CNFG display.
1. From the CNFG display, press the or
buttons to advance to COMM and the BLNC
display.
2. Press the
Set
Point
button to select BLNC. The
display advances to PRI.
3. Press the
Set
Point
button to select PRI.
CNFG
COMM
BLNC
PRI
3 Measure and enter the
actual maximum primary
airflow
The display begins flashing PMAX and also
displays the actual airflow at the bottom.
Note: The airflow will attempt to stabilize on
the highest value for either the cooling or
heating maximum airflow even if only one
mode is operational.
Note: The airflow displayed by the STE-8000
in this step is the actual, uncorrected airflow.
1. Wait for the maximum airflow value to
stabilize.
2. With a flow hood, measure the actual
airflow.
3. Press the
Set
Point
button to advance to the entry
display. PMAX stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the
Set
Point
button to save the measured
airflow. The display changes to PMIN.
PMAX
OO
4 Measure and enter the
actual minimum primary
airflow
The display begins flashing PMIN and also
displays the actual airflow at the bottom.
PMIN
OO
The airflow balancing procedure (continued)
Section 5: Balancing airflow KMC Controls, Inc.
41 Revision G