Procedure Detailed steps STE display
3 Set the primary VAV
terminal unit K-factor.
The K-factor is supplied by the manufacturer of
the VAV terminal unit. Typically it is on the
label with the unit airflow information.
1. Press the or buttons to set the primary
K-factor.
2. Press the
Set
Point
button to save the entry and
advance to the next function.
9O4
PKFT
4 Set the secondary VAV
terminal unit K-factor.
Not used in all models.
The K-factor is supplied by the manufacturer of
the VAV terminal unit. Typically it is on the
label with the unit airflow information.
1. Press the or buttons to set the
secondary K-factor.
2. Press the
Set
Point
button to save the entry and
advance to the next function.
9O4
SKFT
5 Set the mode of reheat
for the terminal unit.
Not used in all models.
1. Press the or buttons to choose one of
the following reheat options.
None—Reheat is not enabled.
StagedEnables staged reheat.
Modulating—The analog reheat output
varies from 0-10 volts DC.
Floating—The reheat outputs control a
tristate actuator.
Time proportionalControls a thermal wax
valve with a 24-volt triac output.
2. Press the
Set
Point
button to save the reheat option
and advance to the next function.
NONE
REHT
6 Set the fan option.
Not used in all models.
1. Press the or buttons to choose one of
the following fan options.
None—No fan is connected to the controller.
SeriesThe VAV unit includes a series fan.
ParallelThe VAV unit includes a parallel
fan.
NONE
FAN
Procedure to set the box functions (continued)
Section 4: Configuring the controllers KMC Controls, Inc.