Install Instructions
Table Of Contents
- Contents
- Section 1: About the controllers
- Section 2: Installing the controllers
- Section 3: Changing the room setpoint
- Section 4: Configuring the controllers
- Section 5: Balancing airflow
- Section 6: Application drawings
- Section 7: Sequences of operation
- Section 8: System integration and networking
- Appendix A: K-factors
- Index
Procedure Detailed steps STE display
7 Set the unoccupied
cooling setpoint.
This setpoint is used as the active setpoint when
the space is unoccupied.
1. Press the or buttons to set the
unoccupied cooling setpoint. The setpoint
will change in 0.5° increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
UNCL
8OO
8 Set the unoccupied
heating setpoint.
This setpoint is used as the active setpoint when
the space is unoccupied.
1. Press the or buttons to set the
unoccupied heating setpoint. The setpoint
will change in 0.5° increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
UNHT
62O
9 Set the supply air
temperature changeover
setpoint.
Not used in all models.
This setpoint sets the supply air temperature at
which the controller will change between
heating to cooling.
1. Press the or buttons to set the
changeover setpoint. The setpoint will
change in 1° increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
74
CHNG
10Set the minimum
temperature differential
setpoint.
The minimum allowable temperature value
between the cooling and heating setpoints.
1. Press the or buttons to set the
differential setpoint. The setpoint will change
in 1° increments.
2. Press the
Set
Point
button to save the setpoint and
advance to the next function.
O5
DIFF
11Set the standby
differential setpoint.
The standby setpoint is calculated by adding or
subtracting the offset value to or from the value
of the occupied setpoint.
1. Press the or buttons to set the standby
differential setpoint. The setpoint will change
in 1° increments.
OS
Procedure to set the temperature setpoints (continued)
SimplyVAV Section 4: Configuring the controllers
Revision G 27