Product Overview
Table Of Contents
- Contents
- General Information (All Output Configurations)
- Overview and General Installation
- Mounting Considerations
- Wiring Considerations
- Inputs and Outputs
- Network Wiring
- Configuration Screens
- Custom Programming
- Sample Custom Applications
- CO2 Sensors and DCV
- Custom Web Graphics
- Hospitality and Locked User Interface Modes
- Motion/Occupancy Sensor
- Support
- Important Notices
- BAC-1xx63/1xxx63 Series (6 Relays and 3 Analog Outputs)
- Bills of Materials (BAC-1xx63/1xxx63)
- Sequence of Operation (BAC-1xx63/1xxx63)
- FlexStat (All Models) Common Features
- Space Temperature Setpoints and Modes
- Occupancy Modes
- Optimum Start
- Standby Mode
- Fan Control
- Sensor 2 (Fan Status or Discharge Air Temp)
- Economizer
- DCV (Demand Controlled Ventilation)—General Information
- DCV—Basic Configuration
- DCV—Standard Configuration
- DCV—Advanced Configuration
- Dehumidification
- Humidification (BAC-1x136 and BAC-1xx136 Only)
- Staged Heating and Cooling Parameters
- User Interface Display Backlight
- BAC-1xx63/1xxx63 Applications
- FlexStat (All Models) Common Features
- BAC-1xx36/1xxx36 Series (3 Relays and 6 Analog Outputs)
- BAC-1xx30 Series (3 Relays and 0 Analog Outputs)
- BAC-1xxx53 (5 Relays, 1 Triac, & 3 Analog Outputs)
- Index
FlexStat (General) 7 Application Guide, Rev S
IN4
IN3
GND
IN2
NOTE: Custom programming is required
Inputs
250 ohms
4–20
mA DC
(–)
(+)
4–20 mA Current Input
To use a 4–20 mA current input:
1. Connect an external 250 ohm resistor from input to ground. (Do not
install the resistor inside the FlexStat’s case since the heat generated
by the resistor may skew the temperature readings.) The resistor
converts the 4–20 mA current input to a 1–5 VDC voltage that can be
read by the thermostat’s analog-to-digital converter.
2. Set the corresponding pull-up switches to the 0–12 VDC position.
3. Using BACstage or TotalControl, congure the input device type for a
4–20 mA source.
1
2
3
4
5
6
3
4
3
4
IN4 =
5
6
10K
Ω
0-12 V
5
6
IN3 =
7
8
7
8
IN2 =
7
8
EOL =
Pushed Left Pushed Right
1
2
ONOFF
1
2
10K Ω
0-12 V
10K
Ω
0-12 V
Analog Input Configuration (in BACstage)
External 250 Ohm Resistor for 4–20 mA Current Inputs