Product Overview
Table Of Contents
- Contents
- General Information (All Output Configurations)
- Overview and General Installation
- Mounting Considerations
- Wiring Considerations
- Inputs and Outputs
- Network Wiring
- Configuration Screens
- Custom Programming
- Sample Custom Applications
- CO2 Sensors and DCV
- Custom Web Graphics
- Hospitality and Locked User Interface Modes
- Motion/Occupancy Sensor
- Support
- Important Notices
- BAC-1xx63/1xxx63 Series (6 Relays and 3 Analog Outputs)
- Bills of Materials (BAC-1xx63/1xxx63)
- Sequence of Operation (BAC-1xx63/1xxx63)
- FlexStat (All Models) Common Features
- Space Temperature Setpoints and Modes
- Occupancy Modes
- Optimum Start
- Standby Mode
- Fan Control
- Sensor 2 (Fan Status or Discharge Air Temp)
- Economizer
- DCV (Demand Controlled Ventilation)—General Information
- DCV—Basic Configuration
- DCV—Standard Configuration
- DCV—Advanced Configuration
- Dehumidification
- Humidification (BAC-1x136 and BAC-1xx136 Only)
- Staged Heating and Cooling Parameters
- User Interface Display Backlight
- BAC-1xx63/1xxx63 Applications
- FlexStat (All Models) Common Features
- BAC-1xx36/1xxx36 Series (3 Relays and 6 Analog Outputs)
- BAC-1xx30 Series (3 Relays and 0 Analog Outputs)
- BAC-1xxx53 (5 Relays, 1 Triac, & 3 Analog Outputs)
- Index
BAC-1xx30 Series (3 Relays and 0 Analog Outputs) Section 67 Application Guide S
Bills of Materials (BAC-1xx30)
AHU (Air Handling Unit)—1 Heat and 1 Cool
CAUTION
Relays are for Class-2 voltages (24 VAC) only. Do not connect line
voltage to the relays!
NOTE: See the BAC-1xx30 Installation Guide section for detailed
drawings and input/output connections as well as other im-
portant installation information.
NOTE: Humidity and motion/occupancy sensor options are dependent
on the FlexStat model. In BAC-10130/11130, dehumidication
or economizer options can be selected but not both.
NOTE: See also Sequence of Operation (BAC-1xx30) on page 68.
BILL OF MATERIALS: AHU, 1 Heat and 1 Cool
REFERENCE KMC PART # PART DESCRIPTION
FLEXSTAT BAC-1xx30 BACNET THERMOSTAT, 3 RELAYS
DAT STE-1402 DUCT TEMPERATURE SENSOR
FST CSE-1102 AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
MAT STE-1416 12' DUCT AVERAGING TEMP SENSOR
OAT STE-1451 OUTSIDE TEMPERATURE SENSOR
TX XEE-6311-075 TRANSFORMER, 120/240/277/480:24 VAC, 75 VA
BILL OF MATERIALS: Cooling Unit, 1 Cool
REFERENCE KMC PART # PART DESCRIPTION
FLEXSTAT BAC-1xx30 BACNET THERMOSTAT, 3 RELAYS
DAT STE-1402 DUCT TEMPERATURE SENSOR
FST CSE-1102 AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
TX XEE-6311-075 TRANSFORMER, 120/240/277/480:24 VAC, 75 VA
BILL OF MATERIALS: Heating Unit, 1 Heat
REFERENCE KMC PART # PART DESCRIPTION
FLEXSTAT BAC-1xx30 BACNET THERMOSTAT, 3 RELAYS
DAT STE-1402 DUCT TEMPERATURE SENSOR
FST CSE-1102 AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
TX XEE-6311-075 TRANSFORMER, 120/240/277/480:24 VAC, 75 VA
Heating Unit—1 Heat
Cooling Unit—1 Cool
HPU (Heat Pump Unit)—1 Compressor
BILL OF MATERIALS: HPU, 1 Compressor
REFERENCE KMC PART # PART DESCRIPTION
FLEXSTAT BAC-1xx30 BACNET THERMOSTAT, 3 RELAYS
DAT STE-1402 DUCT TEMPERATURE SENSOR
FST CSE-1102 AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
TX XEE-6311-075 TRANSFORMER, 120/240/277/480:24 VAC, 75 VA