Product Overview
Table Of Contents
- Contents
- General Information (All Output Configurations)
- Overview and General Installation
- Mounting Considerations
- Wiring Considerations
- Inputs and Outputs
- Network Wiring
- Configuration Screens
- Custom Programming
- Sample Custom Applications
- CO2 Sensors and DCV
- Custom Web Graphics
- Hospitality and Locked User Interface Modes
- Motion/Occupancy Sensor
- Support
- Important Notices
- BAC-1xx63/1xxx63 Series (6 Relays and 3 Analog Outputs)
- Bills of Materials (BAC-1xx63/1xxx63)
- Sequence of Operation (BAC-1xx63/1xxx63)
- FlexStat (All Models) Common Features
- Space Temperature Setpoints and Modes
- Occupancy Modes
- Optimum Start
- Standby Mode
- Fan Control
- Sensor 2 (Fan Status or Discharge Air Temp)
- Economizer
- DCV (Demand Controlled Ventilation)—General Information
- DCV—Basic Configuration
- DCV—Standard Configuration
- DCV—Advanced Configuration
- Dehumidification
- Humidification (BAC-1x136 and BAC-1xx136 Only)
- Staged Heating and Cooling Parameters
- User Interface Display Backlight
- BAC-1xx63/1xxx63 Applications
- FlexStat (All Models) Common Features
- BAC-1xx36/1xxx36 Series (3 Relays and 6 Analog Outputs)
- BAC-1xx30 Series (3 Relays and 0 Analog Outputs)
- BAC-1xxx53 (5 Relays, 1 Triac, & 3 Analog Outputs)
- Index
BAC-1xx36/1xxx36 Series (3 Relays and 6 Analog Outputs) Section 60 Application Guide S
BILL OF MATERIALS: AHU, Modulating Heat and Modulating Cool
REFERENCE KMC PART # PART DESCRIPTION
FLEXSTAT
BAC-1xx36/
1xxx36
BACNET THERMOSTAT, 6 RELAY & 3 ANALOG OUTPUTS
R1 REE-3211** MULTI-VOLTAGE CONTROL RELAY, 1.2 VA
CLV
VEB-43xxxBDL
FAIL-SAFE CONTROL VALVE, W/ MEP-5372 2-10 VDC
ACTUATOR, 19 VA
HTV
FOR VALVES, CHOOSE CAPACITY/MODEL FROM KMC DATA SHEET
HUM REE-3112 12/24 VDC CONTROL RELAY, SPDT
DAT STE-1402 DUCT TEMPERATURE SENSOR
FST CSE-1102 AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
MAT STE-1416 12' DUCT AVERAGING TEMP SENSOR
OAT STE-1451 OUTSIDE TEMPERATURE SENSOR
* STE-6011 REMOTE TEMPERATURE SENSOR, TYPE II
* SAE-10xx REMOTE CO
2
SENSOR, SPACE OR DUCT
TX1 XEE-6311-075 TRANSFORMER, 120/240/277/480:24 VAC, 75 VA
CHOOSE ONE OF THE FOLLOWING TRANSFORMERS:
TX2 XEE-6311-075 TRANSFORMER, 120/208/240/480:24 VAC, 75 VA
TX2 XEE-6311-100 TRANSFORMER, 120/240/277/480:24 VAC, 96 VA
*The remote temperature and CO
2
sensor options are not shown in the sample installation
diagrams, and they are available only on BAC-12xxxx/13xxxx/14xxxx models.
**REE-3211 was discontinued. Use CVR11C-0/LD96200 Multi-Voltage Relays instead.
BILL OF MATERIALS: AHU, DAMPER ACTUATORS
REFERENCE
MAX DAMPER
AREA IN FT
2
KMC PART # PART DESCRIPTION
OAD or RTD 6.25 MEP-5372
50 IN·LB FAIL-SAFE ACTUATOR, 2-10VDC,
19VA
OAD or RTD 15 MEP-7252
120 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
25VA
OAD or RTD 22.5 MEP-7552
180 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
25VA
OAD or RTD 40 MEP-7852
320 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
40VA
FCU (Fan Coil Unit)—2 or 4 Pipe, Modulating
BILL OF MATERIALS: FCU, 2-Pipe, Modulating
REFERENCE KMC PART # PART DESCRIPTION
FLEXSTAT
BAC-1xx36/
1xxx36
BACNET THERMOSTAT, 6 RELAY & 3 ANALOG OUTPUTS
R1, R2, R3 REE-3211** MULTI-VOLTAGE CONTROL RELAY, 1.2 VA
VLV VEB-43xxxBCK CONTROL VALVE W/ MEP-4002 0-10V ACTUATOR, 4 VA
FOR VALVE, CHOOSE CAPACITY/MODEL FROM KMC DATA SHEET
DAT STE-1402 DUCT TEMPERATURE SENSOR
FST CSE-1102 AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
W-TMP STE-1454/1455 2" STRAP-ON TEMPERATURE SENSOR (w/ or w/o enclosure)
* STE-6011 REMOTE TEMPERATURE SENSOR, TYPE II
TX XEE-6311-050 TRANSFORMER, 120/240/277/480:24 VAC, 50 VA
*The remote temperature sensor option is not shown in the sample installation
diagrams, and it is available only on BAC-12xxxx/13xxxx/14xxxx models.
**REE-3211 was discontinued. Use CVR11C-0/LD96200 Multi-Voltage Relays instead.
BILL OF MATERIALS: FCU, 4-Pipe, Modulating
REFERENCE KMC PART # PART DESCRIPTION
FLEXSTAT
BAC-1xx63/
1xxx63
BACNET THERMOSTAT, 6 RELAY & 3 ANALOG OUTPUTS
R1, R2, R3 REE-3211** MULTI-VOLTAGE CONTROL RELAY, 1.2 VA
CLV
VEB-43xxxBCK CONTROL VALVE W/ MEP-4002 0-10V ACTUATOR, 4 VA
HTV
HUMV VEB-43xxxBDL
FAIL-SAFE CONTROL VALVE, W/ MEP-5372 2-10 VDC
ACTUATOR, 19 VA
FOR VALVES, CHOOSE CAPACITY/MODEL FROM KMC DATA SHEET
HUM REE-3112 12/24 VDC CONTROL RELAY, SPDT
DAT STE-1402 DUCT TEMPERATURE SENSOR
FST CSE-1102 AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
* STE-6011 REMOTE TEMPERATURE SENSOR, TYPE II
TX XEE-6311-050 TRANSFORMER, 120/240/277/480:24 VAC, 50 VA
*The remote temperature sensor option is not shown in the sample installation
diagrams, and it is available only on BAC-12xxxx/13xxxx/14xxxx models.
**REE-3211 was discontinued. Use CVR11C-0/LD96200 Multi-Voltage Relays instead.