Product Overview
Table Of Contents
- Contents
- General Information (All Output Configurations)
- Overview and General Installation
- Mounting Considerations
- Wiring Considerations
- Inputs and Outputs
- Network Wiring
- Configuration Screens
- Custom Programming
- Sample Custom Applications
- CO2 Sensors and DCV
- Custom Web Graphics
- Hospitality and Locked User Interface Modes
- Motion/Occupancy Sensor
- Support
- Important Notices
- BAC-1xx63/1xxx63 Series (6 Relays and 3 Analog Outputs)
- Bills of Materials (BAC-1xx63/1xxx63)
- Sequence of Operation (BAC-1xx63/1xxx63)
- FlexStat (All Models) Common Features
- Space Temperature Setpoints and Modes
- Occupancy Modes
- Optimum Start
- Standby Mode
- Fan Control
- Sensor 2 (Fan Status or Discharge Air Temp)
- Economizer
- DCV (Demand Controlled Ventilation)—General Information
- DCV—Basic Configuration
- DCV—Standard Configuration
- DCV—Advanced Configuration
- Dehumidification
- Humidification (BAC-1x136 and BAC-1xx136 Only)
- Staged Heating and Cooling Parameters
- User Interface Display Backlight
- BAC-1xx63/1xxx63 Applications
- FlexStat (All Models) Common Features
- BAC-1xx36/1xxx36 Series (3 Relays and 6 Analog Outputs)
- BAC-1xx30 Series (3 Relays and 0 Analog Outputs)
- BAC-1xxx53 (5 Relays, 1 Triac, & 3 Analog Outputs)
- Index
FlexStat (General) 30 Application Guide, Rev S
Reverting UI Modes
Via the User Interface
Reverting to Standard mode can be done through the FlexStat’s user
interface with a combination of buon presses or by changing MSV9’s
values through BACstage or TotalControl. To revert to Standard mode
through the user interface, follow these steps to access the hidden
menus:
1. Press and hold both the Enter and Right buons for at least ve sec-
onds. (If you push the Right buon before Enter while in Hospitality
mode, you will go to the Field B screen.)
2. While continuing to hold those two buons, press the Left buon
and hold all three buons for at least ve seconds.
3. Release the Right buon but continue holding the Left and Enter but-
tons until the FlexStat menu appears (after about ve more seconds).
NOTE: While holding the Left, Right, and/or Enter buons, do not ac-
cidentally also hold the Up or Down buon.
NOTE: The FlexStat menu has view-only About, Date, and Time lines.
The About selection contains the same information as the
About screen in the Standard mode’s Main Menu. The Date
and Time lines simply display the current date and time infor-
mation.
4. To access and make changes in the “hidden” Main Menu, use the
Up/Down buons to navigate to the SECOND blank line below the
Time line and press the Enter buon.
NOTE: Access to this hidden menu is password protected (if both the
Operator and Administrator passwords are not 0000). Entering
either an Operator or Administrator level password accesses
the Main menu (a User password will not work).
5. The menus operate as normal from this point. To return to Standard
mode, navigate to the Advanced > User Interface menu and select
Standard (otherwise, the previously selected mode will continue).
Via BACstage or TotalControl
To revert to Standard mode through BACstage or TotalControl:
1. Change the Present Value of MSV9 from 2 (HOSPITALITY in TotalC-
ontrol) or 3 (LOCKED UI) to 1 (STANDARD).
NOTE: When the FlexStat is restarted, however, MSV9’s Present
Value will revert to the Relinquished Default and the user in-
terface will revert to the previously selected mode. If a quick
conguration change is desired instead of a permanent mode
change, this is a helpful tool.
2. To make the change permanent, change the Present Value AND the
Relinquished Default to the desired value.
NOTE: Do not change the Present Values or Relinquished Defaults
of any other MSVs 1–12. Doing so may make the FlexStat
malfunction!