Product Overview

Table Of Contents
FlexStat (General) 29 Application Guide, Rev S
SYSTEM MODE
AUTO
HEAT
COOL
OFF
–>
Hospitality and Locked User Interface Modes
Selecting UI Modes
USER INTERFACE
MODE:
ROTATION VALUES
SHOW TEMP TENTHS: NO
STANDARD
USER INTERFACE
MODE:
ROTATION VALUES
HOSPITALITY OPTIONS
SETPT CNTRL: SINGLE
HOSPITALITY
Advanced > User Interface toggles the home screen and other menus
between the default Standard mode and other (more restricted) modes.
NOTE: COMPLETE ALL OTHER NECESSARY CONFIGURATION
BEFORE SELECTING HOSPITALITY OR LOCKED UI
MODE! After Hospitality or Locked UI mode is selected, it is
intentionally dicult to revert to Standard mode!
NOTE: As additional security against unauthorized bypass of Hos-
pitality or Locked UI mode from the FlexStat, set at least an
Operator level password. (See the FlexStat Operation Guide.)
Locked UI mode (also known as Mode 3) on the Home screen, but all
buon functions (except the backlight) are locked.
Hospitality mode (also known as Mode 2) has limited menus and is typ-
ically used in hotel rooms. Users typically can change only the setpoint,
system mode, and fan speed. Pushing the Left and Right buons displays
customizable menu selections (dependent on the conguration), such
as System (Auto, Heat, Cool, and O) and Fan (Auto, High, Medium).
(See the FlexStat Operation Guide about Single Setpoint vs. Schedule
options.)
NOTE: Menus depend on the congured options. A three-speed fan
will display Auto, Low, Medium, and High, but a one-speed
fan will only display Auto and On.
NOTE: Auto in System Mode does not currently have an icon imple-
mented with it. Manually selecting Heat or Cool will display
an icon on the Home screen.
Pushing Left Button Goes to Field A Screen
(Field A Selection)
(Field B Selection)
(Optional Programmed Field C Message)
(Pushing Right
Button Goes to
Field B Screen)
(No Field C Screen Exists)
WED 10/01 3:20 PM
COOL
HIGH
WELCOME
HUM: 46% RH
(Hospitality Mode Sample Screens)
NOTE: If this new feature does not work (is “Inactive”) after upgrad-
ing the rmware (especially from R1.3.0.4 or earlier), you may
need to restore the factory default (especially if there is custom
programming or conguration in the FlexStat) and recongure
the FlexStat. See the FlexStat Operation Guide for information.
Custom Hospitality mode programming is required for:
Use of Field C for displaying messages.
Creating additional/alternate menu options.
Any use of AHU or RTU applications in rmware R1.3.0.11. (Firm-
ware earlier than R1.3.0.11 did not support Hospitality mode at all,
and R1.3.0.11 natively supported only FCU or HPU applications in
Hospitality mode. The latest rmware supports all the applications.)
See Programming Custom Text for Hospitality Mode on page 32 and
Custom Programming on page 17.
Pushing Enter Button Toggles
°F/°C Temperature Scale
(Rotation Value)