Product Overview

Table Of Contents
FlexStat (General) 28 Application Guide, Rev S
76.83 °F
UI SETPT (AV27):
Use this to temporarily change
space temp. setpoint for the
duration of the override timer
(AV16). *(9)
72.00
0
1.00
74.00
72.00
80.00
64.00
*(8) = Writing at priority level 8 will synchronize with the user interface (neither locks the other out).
*(9) = Writing (AV27 and BV2) at priority level 9 will synchronize with user interface programs.
OVERRIDE TIME (AV16):
If set to 0, override will last until
the next schedule event. *(8)
32.68 %RH
SETPT OVERRIDE MODE (BV2):
Use this to remove override or view if
schedule setpoints are overriden. *(9)
OCC COOLING SETPT
(AV20) *(8)
OCC HEATING SETPT
(AV21) *(8)
UNOCC COOLING SETPT
(AV4) *(8)
UNOCC HEATING SETPT
(AV5) *(8)
SPACE HUMIDITY (AI5/AV22)
SPACE CO2 (AI10/AV78)
OAT (AI4/AV23)
Custom Web Graphics
When creating web graphics pages in TotalControl or BACstage, the
following objects are the most commonly used.
NOTE: To prevent locking out the FlexStat’s user interface and pro-
grams, be careful about writing to correct priority levels. See
the *(8) and *(9) notes in the illustration below. If locking out
the FlexStat’s user interface is desired, write to a higher priority
level (i.e., 7/8) from the web interface. If, on the other hand, the
FlexStat’s user interface should always have priority, then write
to a lower priority level (9/10).
NOTE: For information about creating
a graphical web page inter-
face, see the Help systems in
TotalControl or BACstage.
NOTE: For FlexStat application
graphic templates to use
in TotalControl (as shown
above), download KMC’s
Library of Standard Applica-
tions package from the KMC
web site. For FlexStat device
images, download the FlexStat
Device Drawings and Images
collection.
NOTE: See also the Alarms
and (Advanced)
Trend Logs sec-
tions in the Flex-
Stat Operation
Guide for more
objects.