Install Instructions

BAC-12xx63/13xx63/14xx63 Series FlexStat 9 Installation Guide, Rev. E
© 2017 KMC Controls, Inc. 913-019-21E
Important Notices
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) this device may not cause harmful interference,
and (2) this device must accept any interference
received, including interference that may cause
undesired operation. A BAC-12xxxx Class B digital
apparatus complies with Canadian ICES-003. A
BAC-13xxxx/14xxxx Class A digital apparatus com-
plies with Canadian ICES-003 Class A.
Fan Coil Unit (FCU)—Other Options
N.O.
N.C.
(4-PIPE 2-POSITION FCU OPTION)
VEP-1xxx0186/VEZ-4xxxxMBx
Valves with 24 VAC Actuators
XEE-6311-050 Transformer
BRN (VEP Series) or RED (VEZ Series
)
BLU (VEP Series) or BLK (VEZ Series
)
(See Wire
Colors
Above
)
(2-PIPE MODULATING FCU OPTION)
XEE-6311-050 Transformer
STE-1454 Temp. Sensor
VEB-43 Valve with MEP-4002V Actuator
SET SWITCHES FOR...
OPERATION: CCW
INPUT RANGE: 0–10 VDC
(2-PIPE 2-POSITION FCU OPTION)
XEE-6311-050 Transformer
VEP-1xxx0186/VEZ-4xxxxMBx
Valve with 24 VAC Actuator
BRN (VEP Series) or RED (VEZ Series
)
BLU (VEP Series) or BLK (VEZ Series
)
STE-1454
Temp. Sensor
NOTE: See the FCU—Overview section on the
previous page for the 4-Pipe Modulating
option and the general schematic.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250; Fax 574.831.5252
www.kmccontrols.com; info@kmccontrols.com
Additional Resources
The latest support les are always available on the
KMC Controls web site (www.kmccontrols.com). To
see all available les, you will need to log-in to the
Partners site
For specications and accessories, see the BAC-
12xxxx/13xxxx/14xxxx Series FlexStat Data Sheet.
For operation, conguration, troubleshooting, and
other information, see the FlexStat Operation Guide.
For additional wiring, application, and programming
information, see the FlexStat Application Guide.
For additional instructions on programming, see the
Help system for BACstage or TotalControl.
NOTE: In FCU rmware earlier than R2.1.0.18, an
option for a DAT on IN2 was available for
a built-in trend log. For later rmware, use
KMC Connect or TotalControl to create a
custom trend if this is desired.