Product Overview
Table Of Contents
- Contents
- General Information (All Output Configurations)
- Overview and General Installation
- Mounting Considerations
- Wiring Considerations
- Inputs and Outputs
- Network Wiring
- Configuration Screens
- Custom Programming
- Sample Custom Applications
- CO2 Sensors and DCV
- Custom Web Graphics
- Hospitality and Locked User Interface Modes
- Motion/Occupancy Sensor
- Support
- Important Notices
- BAC-1xx63/1xxx63 Series (6 Relays and 3 Analog Outputs)
- Bills of Materials (BAC-1xx63/1xxx63)
- Sequence of Operation (BAC-1xx63/1xxx63)
- FlexStat (All Models) Common Features
- Space Temperature Setpoints and Modes
- Occupancy Modes
- Optimum Start
- Standby Mode
- Fan Control
- Sensor 2 (Fan Status or Discharge Air Temp)
- Economizer
- DCV (Demand Controlled Ventilation)—General Information
- DCV—Basic Configuration
- DCV—Standard Configuration
- DCV—Advanced Configuration
- Dehumidification
- Humidification (BAC-1x136 and BAC-1xx136 Only)
- Staged Heating and Cooling Parameters
- User Interface Display Backlight
- BAC-1xx63/1xxx63 Applications
- FlexStat (All Models) Common Features
- BAC-1xx36/1xxx36 Series (3 Relays and 6 Analog Outputs)
- BAC-1xx30 Series (3 Relays and 0 Analog Outputs)
- BAC-1xxx53 (5 Relays, 1 Triac, & 3 Analog Outputs)
- Index
FlexStat (General) 9 Application Guide, Rev S
MAIN MENU
ABOUT
ADVANCED
ALARM
DATE/TIME
DCV
SCHEDULE
SETPOINTS
ADVANCED
APPLICATION
CB PROGRAMS
COMMUNICATION
CO2 SENSOR
DATE/TIME
DEVICE
INPUTS
INPUTS
1: SPACE TEMP
2: DISCH AIR TEMP
3: MIXED AIR TEMP
4: OUTSIDE AIR TEMP
5: SPACE HUMIDITY
7: REMOTE SPACE TEMP
8: AI_08
SPACE TEMP SENSOR
VALUE: 74.5° F
CAL. OFFSET:
OUT-OF-SERVICE: FALSE
0.0
To CALIBRATE the space sensor from the FlexStat MENU:
NOTE: For maximum accuracy after an initial power-up, let the Flex-
Stat warm up for at least a half hour before calibration.
4. Press the Right arrow buon until the Main Menu appears and
then navigate through the Advanced > Inputs > Space Temp Sensor
menus. (Enter a password as needed.)
5. Push the Down buon and Enter buon to select the Calibration
Oset.
6. Use the Up and Down buons to enter the appropriate oset value
(e.g., –2.1) and press the Enter buon to save.
7. Press the Left buon until the home screen appears.
To CALIBRATE the space sensor using SOFTWARE (BACstage or
TotalControl), navigate to the AI1 input object screen and change the
Oset/Calibration value.
NOTE: In TotalControl, right-click in the Present Value eld of the
AI1 input object screen and select Calibrate Present Value.