Product Overview

Table Of Contents
FlexStat (General) 9 Application Guide, Rev S
MAIN MENU
ABOUT
ADVANCED
ALARM
DATE/TIME
DCV
SCHEDULE
SETPOINTS
ADVANCED
APPLICATION
CB PROGRAMS
COMMUNICATION
CO2 SENSOR
DATE/TIME
DEVICE
INPUTS
INPUTS
1: SPACE TEMP
2: DISCH AIR TEMP
3: MIXED AIR TEMP
4: OUTSIDE AIR TEMP
5: SPACE HUMIDITY
7: REMOTE SPACE TEMP
8: AI_08
SPACE TEMP SENSOR
VALUE: 74.5° F
CAL. OFFSET:
OUT-OF-SERVICE: FALSE
0.0
To CALIBRATE the space sensor from the FlexStat MENU:
NOTE: For maximum accuracy after an initial power-up, let the Flex-
Stat warm up for at least a half hour before calibration.
4. Press the Right arrow buon until the Main Menu appears and
then navigate through the Advanced > Inputs > Space Temp Sensor
menus. (Enter a password as needed.)
5. Push the Down buon and Enter buon to select the Calibration
Oset.
6. Use the Up and Down buons to enter the appropriate oset value
(e.g., –2.1) and press the Enter buon to save.
7. Press the Left buon until the home screen appears.
To CALIBRATE the space sensor using SOFTWARE (BACstage or
TotalControl), navigate to the AI1 input object screen and change the
Oset/Calibration value.
NOTE: In TotalControl, right-click in the Present Value eld of the
AI1 input object screen and select Calibrate Present Value.