Product Overview
Table Of Contents
- Contents
- General Information (All Output Configurations)
- Overview and General Installation
- Mounting Considerations
- Wiring Considerations
- Inputs and Outputs
- Network Wiring
- Configuration Screens
- Custom Programming
- Sample Custom Applications
- CO2 Sensors and DCV
- Custom Web Graphics
- Hospitality and Locked User Interface Modes
- Motion/Occupancy Sensor
- Support
- Important Notices
- BAC-1xx63/1xxx63 Series (6 Relays and 3 Analog Outputs)
- Bills of Materials (BAC-1xx63/1xxx63)
- Sequence of Operation (BAC-1xx63/1xxx63)
- FlexStat (All Models) Common Features
- Space Temperature Setpoints and Modes
- Occupancy Modes
- Optimum Start
- Standby Mode
- Fan Control
- Sensor 2 (Fan Status or Discharge Air Temp)
- Economizer
- DCV (Demand Controlled Ventilation)—General Information
- DCV—Basic Configuration
- DCV—Standard Configuration
- DCV—Advanced Configuration
- Dehumidification
- Humidification (BAC-1x136 and BAC-1xx136 Only)
- Staged Heating and Cooling Parameters
- User Interface Display Backlight
- BAC-1xx63/1xxx63 Applications
- FlexStat (All Models) Common Features
- BAC-1xx36/1xxx36 Series (3 Relays and 6 Analog Outputs)
- BAC-1xx30 Series (3 Relays and 0 Analog Outputs)
- BAC-1xxx53 (5 Relays, 1 Triac, & 3 Analog Outputs)
- Index
FlexStat (General) 22 Application Guide, Rev S
Displaying the Current Setpoint
Method 1
WED 11/19 3:20 PM
COOL:
OCC:
FAN:
SET HUM: 43% RH
From the Home (temperature display) screen, press the Up or Down
arrow buon ONCE to view the current setpoint. (Pressing it more than
once will change the setpoint and start the override mode.) The setpoint
will display for approximately ten seconds.
Method 2
WED 11/19 3:20 PM
COOL:
OCC:
FAN:
SETPOINT: 76° F
At the lower right of the Home screen is a eld that can potentially dis-
play several object Present Values. To permanently display the setpoint
in this eld, use BACstage or TotalControl to do the following:
1. Change AV25 Description to “UI mapped value #4, <SETPOINT>
Current Setpoint” and congure units for ° F (or ° C as needed).
2. Write the following Control Basic program to assign the current set-
point present value (AV27) to AV25 and congure it to auto-run:
AV25 = AV27
3. Restart the FlexStat.
NOTE: If several readings (objects) are congured to show in the eld,
the eld will sequentially show each one. For models with
humidity sensors (which display HUM: xx%), changing AV22’s
description to “UI mapped value #1, <HUMIDITY> space
humidity” will make the length and spacing of the alternating
setpoint and humidity objects display more consistently.
Method 3
When creating web graphics pages in TotalControl or BACstage, AV27
(the current setpoint) can be monitored and altered from a web page.
See Custom Web Graphics on page 28.
See also Displaying Outside Air Temperature on page 23 and Display-
ing Other Objects on page 23.